  Process Cooling Systems Since 1986



Air - Conditioner Selection Guide :
Formula for calculating required cooling capacity:
Q = Q1 + Q2
Q = Total heat load (watts)
Q1 = Heat load due to exposed area of panel (watts)
Q2 = Internal heat load due to electrical/electronics devices (watts)
Q1 = Area (sqm) x 5.5 x T (°C)
  Area - Exposed surface area of enclosure in square meter
  5.5 - Heat transfer co-efficient for metal surface
  T - Temperature difference between Max. ambient and Max. allowable panel temperature
  Q2 - Contact factory for more information on internal heat load calculation
Conversion
  1KW = 1000 W
1KW = 860 kcal/h
1TR = 3000 kcal/h
1TR = 12000 BTU/h

Selection chart for classic series :


COOLING 
CAPACITY
kcal/h 400 900 1400 2000 2300 3000 4500 4500 6000 6000
Watts 465 1047 1628 2326 2675 3500 5250 5250 7000 7000
Refrigerant R 134a 134a 134a 134a 22 22/134a 22/134a 22/134a 22/134a 22/134a
SIDE MOUNTING
Power Supply   1PH 1PH 1PH 1PH 1PH 1PH        
Power KW 0.3 0.3 0.9 1.5 1.5 1.9        
Current A 2 3 5 7.5 6.5 8.5        
HOSE CONNECTING
Power Supply   1PH 1PH 1PH 1PH 1PH 1PH 1PH 3PH 1PH 3PH
Power KW 0.35 0.65 0.9 1.2 1.3 1.8 2.3/2.2 2.2/2.2 2.9/2.9 2.9/2.9
Current A 2 3 5 7 6 8.5 9.5/11.5 4.5/4.5 14/16 6/5.5
TOP MOUNTING
Power Supply   1PH                  
Power KW 0.7                  
Current A 3.5                  
                       
  • THe Ac's are designed to maintain a panel temperature of 5 deg. C to 8 deg. C below the ambient temperature at the site of installation for all non-insulated panels
  • The RH inside the panel can be maintained between 45 to 50 during humid weather conditions
  • Temperature- setting should be made between 25 deg. C to 35 deg. C for healthy operation of electronics and the sir conditioner
  • Settings below 25 deg. C can cause condensation of moisture inside the panel
  • It is essential to seal all openings in the panel before installing the air conditioner
  • All the above capacities are rated at 35 deg. C ambient temperature and 27 + 2 deg. C panel temperature
  • R134a models are best suited for high ambient operation up to 45 deg. C
  • The air conditioners are tested for reliability and performance in a climatic test chamber at peak loads and 45 deg. C chamber temperature
  • Power supply- 1PH, 230V, 50 HZ,AC and 3 PH, 440V, 50 HZ, AC
  • Contact sales department for cut-out and dimensional drawings